Mudd-Slide™ - 20 GL drum

Neutral pH Hard Water Scale Remover
Item #116128

Mudd-Slide™ - 20 GL drum

Neutral pH Hard Water Scale Remover
Item #116128

Need Assistance? Call us 1-800-321-8180

  • Sludge and mud control product
  • Removes hard water deposits
  • Should be used with State’s chemical cooling and boiler products

Product Description

Mudd-Slide™ is a concentrated sludge-and mud-control product designed to be used in conjunction with State Chemical’s cooling or boiler water treatment products. Mudd-Slide is a polymer-based product specifically formulated to prevent the buildup of scale and other deposits in steam boilers, heat exchangers, cooling towers, condensers, compressors, holding tanks, and pipelines. These deposits reduce system efficiency, and increase fuel and electrical costs over time.

APPLICATION
Mudd-Slide can be fed directly from the shipping container, or it can be diluted. Mudd-Slide can also be mixed with the base treatment program to increase sludge and scale control in heavily-fouled systems.

CERTIFIED
Mudd-Slide is NSF certified G6 and is acceptable for treating boilers or steamlines where steam produced may contact edible products.

Directions for Use

Steam Boiler Water Systems. Mudd-Slide™ is not intended as the sole treatment program. Add Mudd-slide when increased scale formation is possible such as when the softener system is not functioning properly. Also add Mudd-Slide to increase scale and sludge removal from boiler systems that are scaled or fouled. Add Mudd-Slide at a rate of 1.0 - 2.0 pints per 1000 gallons of blow down. Mudd-Slide can also be mixed with the base boiler water treatment up to 10 % by volume. Do not mix with SuperHot.

Cooling Tower System: Mudd-slide is not intended as the sole treatment program. Add Mudd-Slide when increased scale control is needed or to remove mud from cooling systems. Add Mudd-slide at a rate of 1.0 - 2.0 pints per 1000 gallons of cooling tower bleed. Do not mix Mudd-Slide with any State Industrial Products biocides.

Cooling Tower Cleaning: 1. Heavily bleed the cooling tower to reduce TDS levels equal to the make up water TDS. 2. Discontinue bleed and close bleed valve for 48 hours. 3. Slug feed 2.5 gallons of Mudd-Slide per 1000 gallons of water in the cooling tower or sump. 4. Circulate the system water for 24 - 48 hours. 5. Heavily bleed the cooling tower or flush to remove all sludge. 6. Repeat if needed. 7. Return the cooling system to normal chemical treatment and bleed control. Note: Mudd-Slide cleaning will remove calcium corbonate hard water scale and mud. Because of poor flow patterns in many evaporative condenser systems, Mudd-slide may not remove all scale in these systems. Note: Avoid contamination of food during use and storage of this product.